4.9.8 - MODES menu
   
m_limit No/Yes - Capacity limit active
m_night No/Yes - Night mode active
m_auto No/Yes - Change-over auto active (not used)
m_defr_a No/Yes - Defrost active, circuit A (not used)
m_defr_b No/Yes - Defrost active, circuit B (not used)
m_sst_a No/Yes - Low SST, circuit A
m_sst_b No/Yes - Low SST, circuit B
m_dgt_a No/Yes - High DGT, circuit A
m_dgt_b No/Yes - High DGT, circuit B
m_hp_a No/Yes - High pressure override, circuit A
m_hp_b No/Yes - High pressure override, circuit B
m_sh_a No/Yes - High superheat, circuit A
m_sh_b No/Yes - High superheat, circuit B
4.9.9 - ALARMS menu
 
ALARMRST Alarm reset
CUR_ALRM Current alarms
ALMHIST1 Alarm history
4.9.10 - ALARMST menu
   
RST_ALM No/Yes - Alarm reset
ALM - - Alarm status
alarm_1c - - Current alarm 1
alarm_2c - - Current alarm 2
alarm_3c - - Current alarm 3
alarm_4c - - Current alarm 4
alarm_5c - - Current alarm 5
alarm_1 - - JBus alarm 1 active
alarm_2 - - JBus alarm 2 active
alarm_3 - - JBus alarm 3 active
alarm_4 - - JBus alarm 4 active
alarm_5 - - JBus alarm 5 active
4.9.11 - CUR_ALRM menu
This menu lists up to ten a active alarms. For each alarm the
display shows the time and date the alarm was generated
as well as the alarm description. Each screen shows one
alarm.
…\ALARMS\CUR_ALM
HH:MM DD-MM-YY : alarm text
Alarm #1
4.9.12 - ALMHIST1 menu
This menu lists up to twenty alarms that have occurred at
the unit. For each alarm the display shows the time and date
the alarm was generated as well as the alarm description.
Each screen shows one alarm.
…\ALARMS\ALMHIST1
HH:MM DD-MM-YY : alarm text
Alarm #1