Carrier Pro-Dialog CONTROL 4 Manual de usuario Pagina 16

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 20
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 15
16

This contact checks the status of a loop (air flow switch
and customer safety loop, see chapter 3.6). It prevents the
unit from starting if it is open when the delay at start-up has
expired. This open contact leads to an alarm shut-down, if
the unit is running.

The control point represents the air temperature that the
unit must control.
Control point = active setpoint + reset
5.3.1 - Active setpoint
Two setpoints can be selected. Usually, the second setpoint
is used for unoccupied periods.
Depending on the current operating type, the active setpoint
can be selected:
by choosing the item in the GENUNIT menu,
via the user’s volt-free contacts,
via network commands
via the setpoint timer program (schedule 2).
The following table summarises the possible selections
depending on the control types (local, remote or network)
and the following parameters:
Setpoint select in local control: item LSP_SEL in the
GENUNIT menu permits selection of the active setpoint,
if the unit is in local operating type.
Setpoint selection contacts: setpoint selection contact
status.
Schedule 2 status: schedule for setpoint selection.
 





 

Local sp1 - - Occupied
Local sp2 - - Unoccupied
Local auto - Occupied Occupied
Local auto - Unoccupied Unoccupied
Remote - sp1 - Occupied
Remote - sp2 - Unoccupied
CCN sp1 - - Occupied
CCN sp2 - - Unoccupied
CCN auto - Occupied Occupied
CCN auto - Unoccupied Unoccupied
5.3.2 - Reset
Reset means that the active setpoint is modified so that less
machine capacity is required. This modification is in
general a reaction to a drop in the load. For the Pro-Dialog
control system, the source of the reset can be configured in
the SETPOINT menu: it can be provided either by the
outdoor temperature (that gives a measure of the load
trends for the building) or imposed by the user.
In response to a drop in the outdoor temperature or to
user reset, the setpoint is reset to optimise unit performance
or enhance comfort.
If correction, based on the outdoor temperature is selected,
it is in accordance with the diagram below.

A SETPOINT/corhioat
B SETPOINT/corlooat
C SETPOINT/oat1_cor
D SETPOINT/oat2_cor
-3
-1
0
1
3
-20
0
10
20
A
B
C
D
40
OAT, °C
Setpoint correction = f(OAT)

The demand limit is used to restrict the unit power consump-
tion. The Pro-Dialog control system allows limitation of
the unit capacity, using user-controlled volt-free contacts.
The unit capacity can never exceed the limit setpoint acti-
vated by these contacts. The limit setpoints can be modified
in the SETPOINT menu.

The night period is defined (see GENUNIT configuration)
by a start time and an end time that are the same for each
day of the week. During the night period, the number of
fans operating can be reduced, and the unit capacity may
be limited.

This function adjusts the number of active compressors to
keep the air temperature at its setpoint. The precision with
which this is achieved depends on the air volume, the flow
rate, the load, and the number of stages available on the unit.
The control system continuously takes account of the
temperature error with respect to the setpoint to determine
the optimal moment at which to add or withdraw a capacity
stage.
If the same compressor undergoes too many starts (per
hour) or runs below one minute each time it is started this
automatically brings about reduction of compressor starts,
which makes the controlled air temperature less precise.
The high and low pressure unloading functions can also affect
temperature control accuracy. Compressors are started and
stopped in a sequence designed to equalise the number of
start-ups (value weighted by their operating time).
Vista de pagina 15
1 2 ... 11 12 13 14 15 16 17 18 19 20

Comentarios a estos manuales

Sin comentarios