20
When an alarm is detected, the ICVC default screen will
freeze (stop updating) at the time of alarm. The freeze enables
the operator to view the chiller conditions at the time of alarm.
The STATUS tables will show the updated information. Once
all alarms have been cleared (by pressing the soft-
key), the default ICVC screen will return to normal operation.
An alarm condition must be rectified before a RESET will
be processed. However, an alert will clear automatically as
soon as the associated condition is rectified.
ICVC MENU ITEMS — To perform any of the operations
described below, the PIC III must be powered up and have
successfully completed its self test. The self test takes place
automatically, after power-up.
Press the softkey to view the list of menu struc-
tures: , , , and
. See Fig. 16.
• The STATUS menu allows viewing and limited calibration
or modification of control points and sensors, relays and
contacts, and the options board.
• The SCHEDULE menu allows viewing and modification of
the local and CCN time schedules and Ice Build time sched-
ules.
• The SETPOINT menu allows set point adjustments, such as
the entering chilled water and leaving chilled water set
points.
• The SERVICE menu can be used to view or modify infor-
mation on the Alarm History, Control Test, Control Algo-
rithm Status, Equipment Configuration, VFD Configuration
data, Equipment Service, Time and Date, Attach to Net-
work Device, Log Out of Network Device, and ICVC Con-
figuration screens. See Fig. 17.
Press the softkey that corresponds to the menu structure to
be viewed: , , , or
. To view or change parameters within any of these
menu structures, use the and softkeys
to scroll down to the desired item or table. Use the
softkey to select that item. The softkey choices that appear next
depend on the selected table or menu. The softkey choices and
their functions are described below.
BASIC ICVC OPERATIONS (Using the Softkeys) — To
perform any of the operations described below, the PIC III
must be powered up and have successfully completed its self
test.
• Press to leave the selected decision or field without
saving any changes.
• Press to leave the selected decision or field and
save changes.
• Press to scroll the cursor bar down in order to
highlight a point or to view more points below the current
screen.
• Press to scroll the cursor bar up in order to
highlight a point or to view points above the current screen.
• Press to view the next screen level (high-lighted
with the cursor bar), or to override (if allowable) the high-
lighted point value.
• Press to return to the previous screen level.
• Press or to change the high-
lighted point value.
RUNNING TEMP CONTROL
LEAVING CHILLED WATER
01-01-95 11:48
28.8 HOURS
CHW IN CHW OUT EVAP REF
CDW IN CDW OUT COND REF
OIL PRESS OIL TEMP % AMPS IN
CCN LOCAL RESET MENU
55.1 44.1 40.7
85.0 95.0 98.1
21.8 132.9 93
PRIMARY STATUS
MESSAGE
COMPRESSOR
ON TIME
DATE TIME
SOFT KEYS
MENU
LINE
EACH KEY'S FUNCTION IS
DEFINED BY THE MENU DESCRIPTION
ON MENU LINE ABOVE
ALARM LIGHT
(ILLUMINATED
WHEN POWER ON)
STOP BUTTON
•
HOLD FOR ONE
SECOND TO STOP
•
•
BLINKS CONTINUOUSLY
ON FOR AN ALARM
BLINKS ONCE TO
CONFIRM A STOP
SECONDARY
STATUS
MESSAGE
Fig. 14 — ICVC Default Screen
a19-1613
CONTROL TEST
CONTROL ALGORITHM STATUS
EQUIPMENT CONFIGURATION
VFD CONFIGURATION DATA
EQUIPMENT SERVICE
TIME AND DATE
ATTACH TO NETWORK DEVICE
LOG OUT OF DEVICE
ICVC CONFIGURATION
ALARM HISTORY
19XRV_II
SERVICE
Fig. 15 — ICVC Service Screen
a19-1614