7. Press to access the holiday table. The Config-
uration Select table now shows the holiday start month
and day, and how many days the holiday period will last.
8. Press or to highlight the month,
day, or duration.
9. Press to modify the month, day, or duration.
10. Press or to change the
selected value.
11. Press to save the changes.
12. Press to return to the previous menu.
DAYLIGHT SAVING TIME CONFIGURATION — The
BRODEF table also defines Daylight Saving Time (DST)
changes. This feature is by default enabled, and the settings
should be reviewed and adjusted if desired. The following
line-item entries are configurable for both DST “Start” and
“Stop,” and they are defined in Table 8.
To disable the Daylight Savings Time function simply enter
0 minutes for “Start Advance” and “Stop Back.”
Table 8 — Daylight Saving Time Values
START-UP/SHUTDOWN/
RECYCLE SEQUENCE (Fig. 27)
Local Start-Up —
Local start-up (or a manual start-up) is
initiated by pressing the menu softkey on the default
ICVC screen. Local start-up can proceed when the chiller
schedule indicates that the CURRENT TIME and CURRENT
DATE have been established as a run time and date, and after
the internal timers have expired. The timers include a
15-minute start-to-start timer and a 1-minute stop-to-start tim-
er, which together serve to prevent excessive cycling and abuse
of the motor. The value of these timers is displayed as START
INHIBIT TIMER and can be viewed on the MAINSTAT and
DEFAULT screens. Both timers must expire before the chiller
will start. If the timers have not expired, the RUN STATUS
parameter on the MAINSTAT screen will read TIMEOUT.
NOTE: The time schedule is said to be “occupied” if the
OCCUPIED ? parameter on the MAINSTAT screen is set to
YES. For more information on occupancy schedules, see the
sections on Time Schedule Operation (page 25), Occupancy
Schedule (page 42), and To Prevent Accidental Start-Up
(page 78), and Fig. 18.
If the OCCUPIED ? parameter on the MAINSTAT screen
is set to NO, the chiller can be forced to start as follows. From
the default ICVC screen, press the and
softkeys. Scroll to highlight MAINSTAT. Press the
softkey. Scroll to highlight CHILLER START/STOP. Press the
softkey to override the schedule and start the chiller.
NOTE: The chiller will continue to run until this forced start is
released, regardless of the programmed schedule. To release
the forced start, highlight CHILLER START/STOP from the
MAINSTAT screen and press the softkey. This
action returns the chiller to the start and stop times established
by the schedule.
The chiller may also be started by overriding the time sched-
ule. From the default screen, press the and
softkeys. Scroll down and select the current
schedule. Select OVERRIDE, and set the desired override time.
Another condition for start-up must be met for chillers that
have the REMOTE CONTACTS OPTION on the EQUIP-
MENT SERVICE screen set to ENABLE. For these chillers,
the REMOTE START CONTACT parameter on the MAIN-
STAT screen must be CLOSED. From the ICVC default
screen, press the and softkeys. Scroll to
highlight MAINSTAT and press the softkey. Scroll
down the MAINSTAT screen to highlight REMOTE START
CONTACT and press the softkey. Then, press the
softkey. To end the override, select REMOTE
CONTACTS INPUT and press the softkey.
Once local start-up begins, the PIC III performs a series of
pre-start tests to verify that all pre-start alerts and safeties are
within the limits shown in Table 7. The RUN STATUS parame-
ter on the MAINSTAT screen line now reads PRESTART. If a
test is not successful, the start-up is delayed or aborted. If the
tests are successful, the CHILLED WATER PUMP relay ener-
gizes, and the RUN STATUS line now reads STARTUP. See
Table 9.
Five seconds later, the CONDENSER WATER PUMP relay
energizes. Thirty seconds later, the PIC III monitors the chilled
water and condenser water flow devices and waits until the
WATER FLOW VERIFY TIME (operator-configured, default
5 minutes) expires to confirm flow. After flow is verified, the
chilled water temperature is compared to CONTROL POINT
plus
1
/
2
CHILLED WATER DEADBAND. If the temperature is
less than or equal to this value, the PIC III turns off
the CONDENSER WATER PUMP relay and goes into a
RECYCLE mode.
ITEM DEFINITION
Month
1 = January, 2 = February, …,
12 = December.
Day of Week 1 = Monday,…, 7 = Sunday
Week
1 = first occurrence of selected Day of
Week in the selected month, 2 = second
occurrence of the selected Day, etc. This
is not necessarily what one would con-
clude from looking at a standard calendar.
For example, April 7, 2011, is Day 4 Week
1, but April 8, 2011, is Day 5 Week 2.
Time
Time of day in 24-hour format when the
time advance or set back will occur.
Advance/Back
“Advance” occurs first in the year, setting
the time ahead by the specified number of
minutes on the selected date. “Back” sets
the time back by the specified amount
(later in the year).
SELECT
NEXT
PREVIOUS
SELECT
INCREASE
DECREASE
ENTER
EXIT
Fig. 26 — Example of Holiday Period Screen
a19-1624