Carrier XRV Especificaciones Pagina 51

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 190
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 50
51
by the amount configured in the VFD INCREASE STEP pa-
rameter. The VFD will not decrease in speed if SURGE
COUNTS is greater than zero.
The threshold at which a current fluctuation is interpreted as
a surge can be adjusted from the OPTIONS screen. The portion
of the surge threshold attributable to current fluctuations can be
changed by scrolling to the SURGE DELTA % AMPS parame-
ter and adjusting it with the INCREASE or DECREASE soft-
keys. The default setting is 10 %. The SURGE TIME PERIOD
can be adjusted from the OPTIONS screen. Scroll to the
SURGE TIME PERIOD parameter and use the INCREASE or
DECREASE softkey to adjust the surge count time interval.
The default setting is 8 minutes.
SURGE PROTECTION COUNTS are displayed in the
COMPRESS screen. Both SURGE PROTECTION COUNTS
and SURGE COUNTS are displayed in the SURGPREV
screen.
Head Pressure Reference Output (See Fig. 24) —
The PIC III control outputs a 4 to 20 mA signal for the
configurable Delta P (CONDENSER PRESSURE minus
EVAPORATOR PRESSURE) reference curve shown in Fig. 24.
The DELTA P AT 100% (chiller at maximum load condition
default at 50 psi), DELTA P AT 0% (chiller at minimum load
condition default at 25 psi) and MINIMUM OUTPUT points
are configurable in the EQUIPMENT SERVICE-OPTIONS
table. When configuring this output ensure that minimum re-
quirements for oil pressure and proper condenser FLASC ori-
fice performance are maintained. The 4 to 20 mA output from
VFD TB1 terminals 17 and 18 may be useful as a reference
signal to control a tower bypass valve, tower speed control,
condenser pump speed control, etc. Note that it is up to the site
design engineering agent to integrate this analog output with
any external system device(s) to produce the desired effect.
Carrier does not make any claim that this output is directly us-
able to control any specific piece of equipment (that is, without
further control elements or signal conditioning), although it
may be.
The head pressure reference output will be on whenever the
condenser pump is operating. It may also be manually operated
in CONTROLS TEST. When the head pressure differential is
less than the value entered for DELTA P AT 0%, the output will
be maintained at 4 mA.
VFD Start-Up Speed Control — Immediately accel-
erating to a high VFD speed improves the ability of the com-
pressor to compensate for some start-up environments that ex-
ceed condenser water design conditions. The 19XRV chillers
initially accelerate to high VFD speed and then gradually slow
the compressor, if possible, while adjusting the guide vane po-
sition until a stable operating point with improved chiller effi-
ciency is attained.
Following a start command, the PIC III controls internally
set the VFD TARGET SPEED to the smaller of the VFD
MAXIMUM SPEED or the VFD START SPEED. Provided
that the chiller has sufficient capacity, the VFD will continue to
run at the startup speed during Ramp Loading until the chilled
water temperature falls within the CHILLED WATER DEAD-
BAND surrounding the set point. RAMP LOADING ACTIVE
in the SURGPREV screen will indicate YES during Ramp
Loading. The GUIDE VANE DELTA will be equal to zero
when the chilled water temperature is in the CHILLED WA-
TER DEADBAND. The VFD speed will then be ramped
down at one half of the VFD GAIN rate until, surge conditions
are encountered, the VFD MINIMUM SPEED is reached, the
ACTUAL GUIDE VANE POS reaches the GUIDE VANE
TRAVEL LIMIT, or the TARGET VFD SPEED is forced.
VFD RAMPDOWN ACTIVE in the SURGPREV screen will
indicate YES during the rampdown process. The VFD speed
will be regulated by standard capacity control and surge pre-
vention algorithms at the conclusion of the rampdown process.
Lead/Lag Control — The lead/lag control system auto-
matically starts and stops a lag or second chiller in a 2-chiller
water system. A third chiller can be added to the lead/lag
system as a standby chiller to start up in case the lead or lag
chiller in the system has shut down during an alarm condition
and additional cooling is required. Refer to Fig. 16 and 17 for
menu, table, and screen selection information.
NOTE: The lead/lag function can be configured on the LEAD-
LAG screen, which is accessed from the SERVICE menu and
EQUIPMENT SERVICE table. See Table 4, Example 20.
Lead/lag status during chiller operation can be viewed on the
LL_MAINT display screen, which is accessed from the
SERVICE menu and CONTROL ALGORITHM STATUS
table. See Table 4, Example 14.
Lead/Lag System Requirements:
all chillers in the system must have software capable of per-
forming the lead/lag function
water pumps MUST be energized from the PIC III controls
water flows should be constant
the CCN time schedules for all chillers must be identical
Operation Features:
2 chiller lead/lag
addition of a third chiller for backup
manual rotation of lead chiller
load balancing (if configured)
staggered restart of the chillers after a power failure
chillers may be piped in parallel or in series chilled water
flow
COMMON POINT SENSOR USAGE AND INSTALLA-
TION Lead/lag operation does not require a common
chilled water point sensor. However, common point sensors
(Spare Temp #1 and #2) may be added to the CCM module, if
desired.
NOTE: If the common point sensor option is chosen on a
chilled water system, each chiller should have its own common
point sensor installed. Each chiller uses its own common point
sensor for control when that chiller is designated as the lead
chiller. The PIC III cannot read the value of common point
sensors installed on the other chillers in the chilled water
system.
If leaving chilled water control (ECW CONTROL OPTION
is set to 0 [DSABLE] TEMP_CTL screen) and a common
point sensor is desired (COMMON SENSOR OPTION in
LEADLAG screen selected as 1) then the sensor is wired in
Spare Temp #1 position on the CCM (terminals J4-25 and
J4-26).
NON-ZERO
EXAMPLE OF
MINIMUM
REFERENCE
OUTPUT
DELTA P
AT 100%
DELTA P
AT 0%
DELTA P
0 mA 2 mA
4 mA
(0%)
20 mA
(100%)
4 T0 20 mA OUTPUT
Fig. 24 — Head Pressure Reference Output
a19-1658
Vista de pagina 50
1 2 ... 46 47 48 49 50 51 52 53 54 55 56 ... 189 190

Comentarios a estos manuales

Sin comentarios