Table 4 — ICVC Display Data (cont)
EXAMPLE 19 — OPTIONS DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
5. Scroll down to highlight .
6. Press .
NOTE: No variables are available for CCN read or write operation.
DESCRIPTION STATUS UNITS POINT DEFAULT
Auto Restart Option 0/1 DSABLE/ENABLE astart DSABLE
Remote Contacts Option 0/1 DSABLE/ENABLE r_contac DSABLE
Soft Stop Amps Threshold 40-100 % softstop 100
Surge / Hot Gas Bypass
Surge Limit/HGBP Option 0/1/2 srg_hgbp 0
Select: Surge=0, HGBP=1
Low Load HGBP=2
Minimum Load Point
Surge/HGBP Delta Tsmin 0.0-150.0 ^F DTsatmin 45
Surge/HGBP IGVmin 0.0-110.0 % GV_MIN 5.0
Full Load Point
Surge/HGBP Delta Tsmax 0.0-150.0 ^F DTsatmax 70
Surge/HGBP IGVmax 0.0-110.0 % GV_MAX 5.0
Surge Line Shape Factor –1.000-0.000 shapefac –0.040
Surge Line Speed Factor 0.00-3.00 VFD_POW 1.85
Surge Line High Offset 0.1-3.0 SP_HIGH 1.0
Surge/HGBP Deadband 0.5-3 ^F h/jointfilesconvert/353596/bg_db 1
Low Load HGBP
HGBP On Delta T 0.5-10.0 ^F hgb_ton 2.0
HGBP Off Delta T 1.0-10.0 ^F hgb_toff 4.0
Surge Protection
Surge Delta% Amps 5-20 % surge_a 10
Surge Time Period 7-10 MIN surge_t 8
Ice Build Control
Ice Build Option 0/1 DSABLE/ENABLE ibopt DSABLE
Ice Build Termination 0-2 ibterm 0
0=Temp, 1=Contacts, 2=Both
Ice Build Recycle 0/1 DSABLE/ENABLE ibrecyc DSABLE
Refrigerant Leak Option 0/1 DSABLE/ENABLE LEAK_EN DSABLE
Refrigerant Leak Alarm mA 4-20 mA LEAK_MA 20
Head Pressure Reference
Delta P at 0% (4mA) 20-85 PSI HPDPO 25
Delta P at 100% (20mA) 20-85 PSI HPDP100 50
Minimum Output 0-100 % HPDPMIN% 0