Table 7 — Points Display Table
*Mode can be set to OFF, HEAT, WARM-UP, VENT, FAN AND VENT, COOL, DEHUMIDIFY, REHEAT, PRESSURIZATION, EVACUATION, ZERO
CALIBRATION, and COMMISSIONING.
Type can be set to SINGLE DUCT, PARALLEL FAN, SERIAL FAN, and DUAL DUCT.
**Value set to zero if zone configured for Pressure Dependent operation.
††Value set to zero if not configured for ducted type heat.
||Only valid for zones configured as Dual Duct type or Pressure Control.
NOTE: All points are forcible except Terminal Mode (MODE), Terminal Type (TYPE), Primary Damper Position (DMPPOS), and Local Heating
Capacity (HCAP).
Table 8 — Set Point Table
Table 9 — Linkage Maintenance Table
*COOLING, HEATING, WARM-UP, FREECOOL, PRESSURE, EVAC, OFF.
Tabl e Name : P OINT S
DESCRIPTION STATUS/UNITS POINT RANGE ACCESS
Terminal Mode
ASCII (8) MODE * R
Terminal Type
ASCII (8) TYPE R
Controlling Set Point
XXX.X dF CNTSP 40.0 to 245.0 R
Space Temperature
XXX.X dF SPT 40.0 to 245.0 R/W
Primary Airflow
XXXX cfm PRIFLO 0 to 9999** R/W
Primary Damper
Position
XXX%OPEN DMPPOS 0 to 100 R
Supply Air Temperature
XXX.X dF SAT 40.0 to 245.0†† R/W
Local Heating Capacity
XXX% HCAP 0 to 100 R
Terminal Fan
Off / On FAN 0 to 1 R/W
Relative Humidity
XXX.X% RH 0.0 to 100.0 R/W
Air Quality (ppm)
XXXX AQ 0 to 5000 R/W
Secondary Airflow
XXXX cfm SECFLO 0 to 9999|| R/W
Primary Air
Temperature
XXX dF PATEMP 40 to 245 R/W
Heat
Dsa / Ena HEAT 0 to 1 R/W
Table Name: SETPOINT
DESCRIPTION STATUS/UNITS POINT RANGE DEFAULT
Occupied Heat
XX.X dF OHSP 40.0 to 90.0 70.0
Occupied Cool
XX.X dF OCSP 45.0 to 99.9 74.0
Unoccupied Heat
XX.X dF UHSP 40.0 to 90.0 69.0
Unoccupied Cool
XX.X dF UCSP 45.0 to 99.9 75.0
Relative Humidity
XXX.X % RHSP 0.0 to 100.0 60.0
Unocc Relative Humidity
XXX.X % UORHSP 0.0 to 100 100
Air Quality (ppm)
XXXX AQSP 0 to 5000 850
Delta Airflow
XXXX cfm DCFM 9999 to 9999 0
Table Name: LINKAGE
DESCRIPTION STATUS/UNITS POINT RANGE ACCESS
Air Source Bus #
XXX ASBUSNUM NONE
Air Source Element #
XXX ASDEVADR NONE
Master Zone Element #
XXX MZDEVADR NONE
Operating Mode
ASCII (8 char) * ASOPMODE NONE
Air Source Supply Temp
XXX.X dF ASTEMP NONE
Start Bias Time
XXX min STRTBIAS NONE
Average Occ Heat Setpt
XX.X dF AOHS NONE
Average Occ Cool Setpt
XX.X dF AOCS NONE
Average Unoc Heat Setpt
XX.X dF AUHS NONE
Average Unoc Cool Setpt
XX.X dF AUCS NONE
Average Zone Temp
XX.X dF AZT R
Average Occ Zone Temp
XX.X dF AOZT R
Composite CCN Value
XXX.X CCCNVAL 0 to 9999.9 NONE
Occupancy Status (1=Occ)
X OCCSTAT R
Next Occupied Day
XXX NEXTOCCD NONE
Next Occupied Time
XX:xx NEXTOCCT NONE
Next Unoccupied Day
XXX NEXTUNOD NONE
Next Unoccupied Time
XX:xx NEXTUNOT NONE
Previous Unoccupied Day
XXX PREVUNOD NONE
Previous Unoccupied Time
XX:xx PREVUNOT NONE
Maximum Damper Position
XX.X % MAXDMPOS 0.0 to 100.0 R/W
Static Press Reset
X.X H2O PRESVAL 0.0 to 5.0 R/W
Pressure Decrease Value
X.X H2O PRESDECR 0.0 to 5.0 R/W
Pressure Increase Value
X.X H2O PRESINCR 0.0 to 5.0 R/W