Carrier 33ZCSECTRM Especificaciones Pagina 34

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 44
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 33
34
Zone Pressure control can also be used to control systems
utilizing dual duct terminals to supply a constant amount of
ventilation air to each zone. In these systems, a separate venti-
lation air source delivers conditioned, ventilation air to the sec-
ondary inlet of each dual duct terminal. The primary inlet is
connected to a standard VAV air source. The primary airflow is
controlled to maintain the desired space temperature in the
same way as a single duct terminal. A secondary airflow sensor
is installed in the total airflow from terminal and connected to a
secondary damper control. The actuator is installed on the sec-
ondary damper (hot deck or ventilation inlet). As the load
changes and the primary airflow modulates, the airflow sensed
by both the primary inlet and total outlet probes vary. If a nega-
tive value in the amount of the required ventilation airflow is
configured, that difference is introduced by the secondary
damper as ventilation air. In these applications, heating is typi-
cally provided by an auxiliary heat source controlled by the ter-
minal, but may be supplied through the air source as well (VAV
heating). See Fig. 28.
LIMITATIONS The zone controller can not be located in
corrosive and contaminated environments. The terminal con-
troller maximum size damper is limited to 500 sq in. and
9000 CFM. Applying the zone controller in this manner for
zone pressure control will work only if all the air entering the
zone is measured. Therefore all the air supplied to the space
must be supplied through a single duct type terminal. This is
the same for the return zone exhaust air. Only single duct termi-
nals or exhaust dampers can be controlled by a secondary ter-
minal control. The 33ZCFANTRM zone controller and
33ZCESECTRM secondary damper terminal control must be
configured for single duct control. The type of supply and ex-
haust damper do not need to be the same design and stroke
(i.e., opposed blade, 90 degree butterfly, or 35 / 45 degree blade
type).
To maintain a zone at a constant desired pressure (either
negative or positive), the zone controller modulates the second-
ary damper to control the return airflow from the zone. The re-
turn airflow is controlled to an airflow set point that is offset
from the current primary damper airflow set point by a config-
ured delta. If the secondary airflow set point is less than the pri-
mary airflow set point, more air will flow into the zone than
leaves the zone and the zone will be pressurized.
If the secondary airflow set point is greater than the primary
set point, then more air will leave the zone than is entering it
and the zone will be depressurized. As the zone’s temperature
load changes and the primary damper modulates to maintain
the desired temperature set point, the zone controller will mod-
ulate the secondary damper position to maintain the required
difference in airflow and maintain the zone’s static pressure.
TERMINAL TRACKING — For applications where pres-
sure control is required in the occupied space in order to pro-
vide isolation, zone pressure control provides volumetric flow
tracking to maintain the proper return airflow by controlling
a secondary damper connected to the return air system. See
Fig. 27. Zone Pressure Control can only work properly if all the
air entering and leaving the space is measured. Therefore all air
supplied to the space should be supplied through a single duct
type terminal. No provision can be made to disable pressure
control if other than a single duct terminal (fan powered termi-
nal) is configured as the primary air device. In these systems,
the primary air damper is modulated in order to maintain the
space temperature within the desired set points. The primary air
terminal is a single duct terminal, therefore all sequences of
operation, for a single duct terminal apply to the primary
terminal.
Only single duct type terminals should be used for return air
control. If other terminals are used, no provision can be made
to disable pressure control. As the primary airflow set point
changes, the pressure control modules the return damper to
maintain the secondary airflow at a fixed delta (either positive
or negative) from the current primary airflow reference.
Dual Duct Terminal Applications —
The zone con-
troller provides control of a second damper in a dual duct ter-
minal. A dual duct terminal has two primary air inlets, referred
to as the cold deck and the hot deck. The second damper is the
hot deck damper. The dampers are controlled by the
33ZCFANTRM and 33ZCSECTRM zone controllers. The two
inlets provide a source of heating and cooling to the zone. Dual
duct terminals can be controlled in a constant volume mode or
a variable volume mode. Additionally, the constant volume
mode can be controlled using a second inlet airflow probe or a
total airflow probe. These three configurations are shown in
Fig. 29-31. The main difference between the configurations is
the placement of sensors and output control signals.
SECONDARY
AIRFLOW SENSOR
PRIMARY DAMPER
CONTROL OUTPUT
PRIMARY AIRFLOW
DAMPER
SECONDARY
AIRFLOW DAMPER
TOTAL AIRFLOW
PRIMARY AIRFLOW
SENSOR
PRIMARY AIR
VENTILATION AIR
SECONDARY DAMPER
CONTROL OUTPUT
SECONDARY
CONTROLLER
ZONE
CONTROLLER
CONSTANT VENTILATION USING DUCT DUCT TERMINAL
WITH ZONE PRESSURE CONTROL
Fig. 28 — Secondary Damper for Zone Pressurization
Vista de pagina 33
1 2 ... 29 30 31 32 33 34 35 36 37 38 39 ... 43 44

Comentarios a estos manuales

Sin comentarios