18
If the zone controller is configured as a parallel fan type ter-
minal, the zone controller will utilize the fan as the first stage of
heat, regardless of the heat type configured. The amount of
time the fan will operate as the first heat stage is determined by
the value configured for the Heat On Delay (10 to 20 minutes
recommended).
The Heat On Delay is used to prevent mechanical heating
from being operated for a configured period of time. For single
duct type terminals, a delay of 2 minutes (default value) allows
the zone controller to increase the airflow to the desired reheat
cfm before operating heat. For parallel fan type terminals, the
default value is typically increased to 15 minutes to allow the
fan to utilize heat from the ceiling plenum, before any addition-
al mechanical heating is energized.
Disabling Reheat From CCN —
The zone controller
provides a means to disable the reheat function from the CCN.
This is used to prevent zones that use a central heat source from
using local heat. When the central heating source is not produc-
ing hot water or steam heat to the terminals (the boiler is dis-
abled for example), a system mode broadcast can prevent these
terminals from entering reheat mode. By preventing reheat, the
zone controller will control to the minimum cooling CFM rath-
er than the higher reheat CFM. This will prevent more cool air
from entering into the space when heating is actually required.
The HEAT ENABLED variable is located in the display ta-
ble for each zone controller and can be forced from the CCN.
Normally when the zone controller is in heating, this variable
will indicate ENABLE. To disable heating when the central
heat source is off, this variable must be forced to DISABLE.
This force should occur at least once an hour and sent to all
zone controllers that are supplied heat from the central source.
This application will require the use of a Comfort Controller or
data transfer module to accomplish this function.
Non-Ducted Heat Control (Single or Staged
Heat) —
Either zone controller can support the non-ducted
heat function. The non-ducted heat function can be configured
for either single duct units, fan powered parallel, or fan pow-
ered series applications or constant volume dual duct applica-
tions where auxiliary perimeter heat is provided. Heat needs to
be controlled within the zone that is controlled by the terminal
unit. Non-ducted heat can be applied to zone controller units
configured as Dual Duct Units which have additional perimeter
heating.
In a non-ducted heat application, the heating controlled de-
vice is located within the space. The heating device is typically
either a two position (On-Off) device like a hot water valve or
electric baseboard heater. For this application, no heating con-
trol loop feedback is required. The installation of the supply air
sensor is not required when the unit is configured for non–
ducted heat.
Additionally, the zone controller can control a single stage,
two-position, or multistage electric supplemental heat devices.
The zone controller will only use space temperature as feed-
back into the temperature control loop to maintain the heating
set point in these applications.
When the 33ZCVAVTRM or 33ZCFANTRM zone control-
lers are applied and configured for heat, and heating is being
called for in the space, the zone controller reads the space sen-
sor and the output is adjusted to satisfy conditions. The number
of stages (if applicable) is determined by comparing space tem-
perature with the current biased heating set point.
Configuration determines the logic output type for normally
open or normally closed type two-position valves. Hysteresis is
determined by the Heating Proportional Gain configured.
A terminal unit equipped with heating will provide the min-
imum heating CFM configured for the zone whenever the air
source is in heat mode unless VAV central heating is enabled.
The heating control maintains the current heating set point
(plus any offset from a 33ZCT56SPT sensor slide bar during
occupied periods).
Modulating Baseboard Heating —
The zone con-
troller can provide control of modulating hot water (hydronic)
baseboard heating which provides perimeter heating for a zone.
The zone controller can be used with single duct, fan powered,
or dual duct terminals using perimeter hydronic heating. A
field-supplied modulating (floating point type) water valve is
used to control the flow of water through the baseboard hy-
dronic heating coil. A field-supplied accessory temperature
sensor (33ZCSENCHG) attached to the leaving water side of
the hydronic baseboard heating coil is required to properly
modulate the hot water valve.
NOTE: It is strongly recommended to mount both the temper-
ature sensor and the modulating water valve to the leaving side
of the hydronic heater. This will minimize installation time and
improve valve life.
Ducted Heat Control (Staged or Modulating
Device) —
The zone controller can support a ducted heat
function. The ducted heat function can be configured for either
single duct units, fan powered parallel, or fan powered series
applications where heat needs to be controlled within the zone
that is supplied by the terminal unit.
For this application, heating control loop feedback is re-
quired. The installation of the supply air sensor is required
when the unit is configured for ducted heat.
The zone controller can control a single stage, two-position,
multistage electric heat, or a modulating hot water valve.
When the 33ZCVAVTRM or 33ZCFANTRM zone control-
lers are applied and configured for heat, and heating is being
called for in the space, the zone controller reads the space sen-
sor and the output is adjusted to satisfy conditions. The number
of stages (if applicable) is determined by comparing space tem-
perature with the current biased heating set point.
Configuration determines the logic output type for normally
open or normally closed type two-position valves.
A terminal unit equipped with heating will provide the min-
imum heating CFM configured for the zone whenever the air
source is in heat mode unless VAV central heating is enabled.
The heating control maintains the current heating set point
(plus any offset from a 33ZCT56SPT sensor slide bar during
occupied periods).
Modulating Hot Water/Steam Valve CV —
The
Modulating Hot Water/Steam Valve CV mode is designed to
use modulating heat valve with a constant volume airflow. This
mode of operation allows all CFM set points to be set to the
same CFM value. The zone reheat will temper the supply air to
maintain proper zone temperature at the configured constant
volume of air.
VAV Central Heating —
The use of the zone controller
in a system allows for the application of VAV heating utilizing
the heat from a central air source. Typically when a system is
designed, the central heat is used for morning warm up only.
The zone controller provides the ability to add heat to a system
during the occupied mode from a central source. Terminal units
designed without any local heat (ducted or non ducted), should
utilize VAV Heating. During VAV heating, the zone controller
modulates its primary air damper to provide heat when the air
source is in Heat Mode. The airflow is controlled so that the
zone achieves and maintains the desired heating set point.
In VAV central heating, the terminal provides a variable vol-
ume into the zone. The central supply air will be a source of
heating when the air source is in the heating mode.
801
→
Comentarios a estos manuales