Carrier 33ZCSECTRM Especificaciones Pagina 19

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 44
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 18
19
The zone controller temperature control loop determines the
airflow set point that is required to maintain space temperature
at the heating set point. Each zone controller modulates be-
tween the minimum heating cfm and the maximum heating
cfm during central heating. This CFM should be limited to a
configured range of values that allows the air source to operate
properly in the heating mode.
In a system with an air source controlled by CCN device,
the zone controller will notify the corresponding linkage mas-
ter zone controller that the unit is heat mode or in morning
warm up.
In the case of a non-CCN controlled air source, the zone
controller should be set up as the linkage master for that air
source. The zone controller will determine if the primary air
temperature is greater than the weighted average space temper-
ature, and if higher, then declares the central air source in
heating.
VAV Central Heating with Ducted Zone
Heat —
When heating is available at the zone (ducted), and
central heating is also available, the zone heat will work in par-
allel to provide heating to the space. This heating function pro-
vides the required volume of heated air from the central appa-
ratus. This volume is determined by a PID airflow control, the
space temperature, and the desired set point. In addition, the
temperature of the air can be supplemented by the local heat
source, if the current air temperature cannot meet zone require-
ments. Each zone controller configured for heat (ducted or non
ducted) will operate its heating control loop when ever the
space temperature is below the heating set point to determine a
desired supply air discharge temperature that is necessary to
maintain space temperature at the heating set point.
NOTE: Central heat with ducted zone heat requires a supply
air sensor.
Morning Warm-Up —
The zone controller performs
Morning Warm-Up when its air source is in the Morning
Warm-Up mode. During Morning Warm-Up mode, the zone
controller operates the same as it does during heating. The zone
controller uses its occupied heating set point during Morning
Warm-Up, regardless of the current status of Occupancy. For
series fan terminal applications, the zone controller turns on the
air terminal’s fan during Morning Warm-Up operation.
If the zone controller is configured to perform supplemental
heating, it operates as defined for ducted or non-ducted heating
as applicable.
Damper Override —
Damper Override mode is initiat-
ed by the air source in response to input from a field-supplied
smoke control panel. When the air source enters an override
mode the linkage coordinator signals the zone controllers to
take corresponding action. The override can take either of two
forms: pressurization or evacuation. In Pressurization mode,
the zone controller commands the air terminal’s supply air
damper to maximum cool cfm. In Evacuation mode, it com-
mands the damper completely closed.
Damper Override supersedes the cfm setting the zone con-
troller would otherwise maintain based on space temperature.
The smoke control panel that commands the override mode
must be in accordance with local codes, as must its installation.
Nighttime Free Cooling —
Nighttime Free Cooling
(NTFC) is an air handler cooling function that can be em-
ployed during unoccupied periods when conditions permit. If
outside air is acceptable, based on temperature and enthalpy,
during unoccupied early morning hours, the air handler will de-
liver the cool outside air to the air terminals. When the air
source indicates that NTFC is operating, the zone controller at
each air terminal controls to midway between the occupied
heating and occupied cooling set points, rather than to the high-
er unoccupied cooling set point that would otherwise be in ef-
fect at that time.
For series fan terminal applications, the zone controller
turns on the air terminal’s fan during NTFC operation.
NOTE: This feature is only available to CCN systems where
fully compatible linkage air source controls are used.
Single Duct Terminal Applications
When ap-
plying the 33ZCVAVTRM zone controller, ducted heat can
only be used when the air source is on, since the air source is
providing the only means of airflow into the zone.
Either model zone controller can support the Reheat func-
tion for single duct terminals.
With a single duct terminal application, if the central air
source is on and in cooling mode and the terminal is equipped
with heat, then the heat will be used to reheat the supply air to
prevent over cooling of the space. Reheat will occur when the
space temperature drops below the heating set point. The zone
controller will enable the heating control algorithm. At this
point the zone controller will provide primary airflow equiva-
lent to the larger of either the minimum cooling CFM require-
ment (to satisfy the minimum air flow for the air source) or the
reheat CFM requirement (to provide minimum airflow for the
heating coil).
COOLING The primary control function of zone controller
is to provide cooling to the space by modulating the amount of
supply airflow through its primary damper.
The Zone Controller uses pressure independent operation to
control the amount of cool air entering the space. The control
variable is terminal airflow (CFM). A PID temperature control
loop determines the airflow set point needed to maintain space
temperature at the cooling set point.
The airflow set point is limited to a configured range of val-
ues that allow the air source to operate properly in the cooling
mode. These configured limits are listed in the Installation In-
structions for the zone controller. The minimum limit ensures
that the sum of all air terminal minimum requirements fall
within the minimum cooling operating range of the air source.
The maximum limit ensures that airflow will not increase
above the maximum design value and that the noise level gen-
erated at this maximum airflow will be acceptable to the occu-
pants of the zone.
When using VAV Heating, it is the system designers
responsibility that the central apparatus is protected during
heating to provide proper airflow over the central heating
device. Ensure that there will be a minimum system air-
flow that will allow the air source to operate safely in the
heating mode. The zone controller will allow for the option
of disabling the VAV central heating function in a given
zone. This means that a central air source may provide
heating for the entire system, or possibly only provide it for
those terminals without heat at the zone level.
The minimum airflow required by the heat at each terminal
must be configured properly to protect and ensure proper
heat transfer for the heating coil. If the minimum cooling
cfm limit is below the terminal’s recommended minimum
value, use the reheat cfm limit for this configuration. The
minimum heat cfm limit should also be set to this value.
Vista de pagina 18
1 2 ... 14 15 16 17 18 19 20 21 22 23 24 ... 43 44

Comentarios a estos manuales

Sin comentarios