Carrier 33ZCSECTRM Especificaciones Pagina 29

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 44
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 28
29
HOT WATER HEAT The zone controller can be config-
ured to control local heat provided by heating coils carrying hot
water or steam, governed either by a two-position (on/off)
valve or by a proportional (floating modulating) valve. The
heating coils can be installed in the air terminal (ducted), or as
perimeter heat. If modulating baseboard heat is used, refer to
the General Heating Information section for additional infor-
mation. Figure 24 shows the hardware configuration for a zone
controller applied to a parallel fan powered air terminal
equipped with hot water or steam heating coils. The diagram in
Fig. 25 shows how the zone controller controls an air terminal
equipped with two-position hot water or steam heat. The dia-
gram in Fig. 26 shows how the zone controller controls an air
terminal equipped with proportional hot water or steam heat.
The fan runs while the air terminal is heating.
For modulating control, the supply air needed is compared
to the actual supply air to either drive the valve open or closed.
There is a deadband on the supply air deviation where the valve
will be left at the current position until the error gets larger than
the deadband.
Configuration determines the logic output type for normally
open or normally closed type two-position valves.
Heating with IAQ Control
— A feature is provided for situa-
tions in which additional primary air is required for ventilation
(IAQ).
The heating set point is calculated from the midpoint be-
tween the current heating and cooling set points.
The standard heating algorithm is used. The effect is to pre-
vent the space temperature from falling below the set point be-
fore heating is activated. The air terminal must be in the Cool-
ing mode and the equipment must be providing cooling.
When in unoccupied heating, the terminal’s fan will be
turned on to provide airflow to the zone. Also, in the Unoccu-
pied mode, a parallel fan terminal zone controller will keep the
primary damper closed to prevent airflow back into the prima-
ry air duct. If the air source becomes active (on) during this
mode, the damper will be controlled normally.
Static Pressure Reset
OVERVIEW — The static pressure reset function of the zone
controller linkage master will automatically reset the central air
source’s supply-fan static pressure set point (downward) as a
function of the zone damper position. This allows the system to
automatically make adjustments to the static pressure and opti-
mize performance of the central air source fan. The maximum
pressure is determined by the set point configured at the equip-
ment control. The minimum value is determined by the maxi-
mum value configured.
OPERATION Once a minute, the linkage master examines
the state of the air source fan. If the fan is operating, the posi-
tion of each damper serviced by the air source is polled by the
Linkage Master to determine the position of its dampers. If the
fan is off, the algorithm calculates a value of 0 for the reset
value.
With the fan operating, the static pressure function deter-
mines the maximum open damper in the system and compares
that value to the configured reset minimum damper position.
When all of the dampers are below (closed) the configured re-
set minimum damper position, the linkage master calculates a
reset value.
The reset value is communicated to the fan controller in the
air source once every minute. The central air source controller
subtracts the reset value from the air source static pressure set
point.
The central air source controller begins to modulate its fan
volume control mechanism to maintain the new supply static
pressure set point. Each zone controller modulates its termi-
nal’s damper position in order to provide the required pressure
drop or restriction to maintain the zone’s CFM balance point at
this new supply duct pressure. If the static pressure set point
value has been changed, then the linkage master will wait
2 minutes to allow the air source static pressure control to af-
fect the system static pressure before calculating any further re-
set value. If the most open damper in the system is open greater
than the maximum damper position, then the linkage master
calculates a reduction to the previous reset value. This will re-
sult in an increase in static pressure (never greater than the con-
figured set point).
NOTE: Primary air source controllers that support this func-
tion are the AirManager™ control. Comfort Controllers can
support this function by using Best++™ applications available
by contacting the local Carrier representative.
Indoor Air Quality (IAQ) Control —
Each zone con-
troller used in a single duct and fan powered application has the
ability to provide IAQ operation. The IAQ function determines
the zone ventilation airflow as a function of the IAQ zone sen-
sor reading. When the air quality control is enabled, the zone
controller will override (increase) the primary airflow in order
to provide Demand Controlled Ventilation if the airflow is in-
sufficient to meet the ventilation set point.
The control algorithm uses a P/I algorithm to determine the
required airflow in order to prevent the IAQ sensor value from
exceeding the desired Air Quality set point. The zone controller
is designed to interface with the following IAQ sensors that
sense CO
2
:
The 33ZCSENCO2 sensor is an indoor, wall mounted sen-
sor with an LED (light-emitting diode) display. The sensor has
an analog output (0 to 10 vdc) over a range of 0 to 2000 ppm.
An SPDT contact is provided to close at 1000 ppm with a hys-
teresis of 50 ppm.
The 33ZCT55CO2 sensor is an indoor, wall mounted
sensor without display. The CO
2
sensor also includes a space
temperature sensor with override button.
The 33ZCT56CO2 sensor is an indoor, wall mounted
sensor without display. The CO
2
sensor also includes a space
temperature sensor with override button and temperature
offset.
The IAQ function contains a provision to operate modulat-
ing type heat, if required and supplied, to maintain the space
temperature at the midpoint between the heating and cooling
set points during IAQ operation. Operation is dependent upon
the equipment mode of operation, so that the Air Quality func-
tion will only operate during Occupied periods when the out-
door air damper is actively providing ventilation. A user con-
figured AQ Maximum % can be used to protect the zone from
overcooling if local heating is not supplied. Air Quality control
is automatically suspended if the space temperature falls below
the heating set point. Air quality control will be disabled if the
AQ sensor status fails.
Secondary Zone Controller (33ZCSECTRM)
The 33ZCFANTRM zone controller, in conjunction with the
33ZCSECTRM zone controller, can be used for zone pressure
control and dual duct applications. To perform these functions
a secondary damper and a secondary airflow sensor is required.
The type of secondary airflow control (none, pressurization, or
dual duct) is user selectable at each secondary zone controller.
Vista de pagina 28
1 2 ... 24 25 26 27 28 29 30 31 32 33 34 ... 43 44

Comentarios a estos manuales

Sin comentarios