6
Sensor Information —
Each zone controller requires a
Carrier space temperature sensor that must be ordered separate-
ly. There are two space sensors available for this application
the 33ZCT55SPT space temperature sensor with override but-
ton and the 33ZCT56SPT
space temperature sensor with over-
ride button and set point adjustment.
SPACE TEMPERATURE SENSORS — The sensor housing
is plastic ABS. The connections are screw terminals. The
weight is 0.18 lbs. See Fig. 1 for sensor dimensions.
The 33ZCT56SPT space temperature sensor has a set point
potentiometer that provides a set point input. The set point
potentiometer range for each sensor can be adjusted from –15°
to 15° F. Adjustment direction is indicated by COOL and
WARM on the sensor cover.
The temperature sensor uses a 10K Ohm thermistor to sense
ambient temperature. See Table 1 for resistance vs. temperature
values for the thermistor.
The sensor is designed to be mounted in a vertical mounting
position for proper operation.
33ZCT55SPT SENSOR — The 33ZCT55SPT space sensor is
a basic space temperature sensor for use with the zone control-
ler. It contains a thermistor to sense room temperature, override
button for initiating a timed override, and an RJ11 jack for the
connection of a CCN Network Service Tool. The sensor com-
munications connection (RJ11) is concealed behind a remov-
able cover. The sensor is field installed.
Space Temperature Sensor Wiring
— In order to provide
temperature sensing and override functions, the 33ZCT55SPT
sensor must be connected to the zone controller using 20 AWG
twisted pair cables. Pressing the timed override button on the
33ZCT55SPT sensor produces the required short-circuit signal.
See Fig. 2 for internal schematic. The sensor has a screw termi-
nal connector to facilitate wiring. All wiring from the zone con-
troller to the sensor is field supplied.
Sensor terminals 1 and 2 are used for space temperature
sensing. The space temperature sensor range is 32 to 120 F,
with a nominal resistance of 10,000 ohms at 77 F.
33ZCT56SPT SENSOR — The 33ZCT56SPT space temper-
ature sensor is field-installed. The 33ZCT56SPT is a wall
mounted sensor capable of measuring the ambient temperature
at its location, and is equipped with an override button. The
override button (when pressed) provides a short across the in-
ternal thermistor. The sensor is also equipped with an RJ11
Service jack with a 6 pin termination block for CCN connec-
tion. The sensor is equipped with a 100K ohm (nominal) linear
slide potentiometer.
Space Temperature Sensor Wiring
— In order to provide
temperature sensing and the override functions, the
33ZCT56SPT sensor must be connected to the zone controller
using 3-conductor, 18 to 20 AWG cables. (The CCN communi-
cation cable may be used.) Pressing the timed override button
the 33ZCT56SPT sensor produces the required short-circuit
signal. See Fig. 2 for internal schematic. The sensor has a
screw terminal connector to facilitate wiring. All wiring from
the zone controller to the sensor is field supplied. The sensor’s
thermistor has a range of 32 to 158 F with a nominal resistance
of 10,000 ohms at 77 F.
NOTE: Dimensions are in inches.
Fig. 1 — Space Temperature Sensor and Wall
Mounted Humidity Sensor Dimensions
5 4 3 2 1
6
(24 VAC +)
(CCN +)
(CCN GND)
(UNUSED)
(CCN -)
(24 VAC -)
PUSH BUTTON
OVERRIDE
SW1
J3
S1
J4
10K
SENSOR
100K
R3
0 OHMS
SEN
SET
INTERNAL SCHEMATIC
T56 ONLY
RJ-11
SERVICE JACK
Fig. 2 — Temperature Sensor Internal Wiring