Carrier 33ZCSECTRM Especificaciones Pagina 23

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 44
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 22
23
For modulating control, the supply air needed is compared
to the actual supply air to either drive the valve open or closed.
There is a deadband on the supply air deviation where the valve
will be left at the current position until the error gets larger than
the deadband.
For modulating type heat, the floating point function com-
pares the submaster reference from the PID loop to the supply
air temperature to calculate the direction and time to position
the valve. The control prevents both outputs from operating si-
multaneously.
Configuration determines the logic output type for normally
open or normally closed type two-position valves. Hysteresis is
determined by the Heating Proportional Gain configured.
Heating with IAQ Control
— A feature is provided for situa-
tions in which additional primary air is required for ventilation
(IAQ).
The heating set point is calculated as the midpoint between
the current heating and cooling set points.
The standard heating algorithm is used except the control
set point is raised. The algorithm prevents the space tempera-
ture from falling below the set point before heating is activated.
The air terminal must be in the cooling mode and the equip-
ment must be providing cooling.
33ZCFANTRM VAV Zone Controller Informa-
tion —
The zone controller will control the operation of the
fan (start and stop), whenever the zone controller is configured
for use with a series or parallel fan terminal. The control algo-
rithm determines the required fan state, based on the local
mode, equipment mode, and the terminal type configuration.
For parallel or intermittent fan powered terminals (type 2
configuration), the fan operates as follows:
1. The fan is energized:
a. When ever SPT< current heating set point
The primary air damper is set to the fully closed
position if the air source mode is OFF and heating
is required. After heating is disabled, or if the
equipment begins to operate, the primary air
damper returns to normal operation.
b. If the Primary Damper Reference drops below the
configured Parallel Fan On value
2. The fan is deenergized:
a. Whenever SPT > current heating set point and
heating is disabled
b. If the Primary Damper Reference rises above the
configured Parallel Fan ON value
For series or constant volume fan powered terminals (type 3
configuration), the fan operates as follows:
1. The fan is energized:
a. During occupied periods
b. Whenever SPT < current heating set point
c. Whenever the air source mode is not off
NOTE: Whenever the terminal fan transitions to
ON, a fan start-up routine will run to ensure the
fan rotates in the proper direction.
2. The fan is deenergized:
a. If in Unoccupied mode and heating is not
required, or if the air source is off
b. during the fan start-up routine.
Series Fan Terminal Applications —
In a series
fan terminal, the fan is located in the primary air stream and,
therefore, must be running in order to achieve proper airflow.
The series fan terminal allows for a variable temperature, con-
stant volume airflow. Maintaining constant volume airflow is
not a function of the zone controller. The fan itself will main-
tain a constant airflow. Therefore, as the primary airflow is
modulated to control temperature, more or less air will be in-
duced from the return air plenum to maintain constant volume
airflow.
The fan is turned on whenever the central air source is on, or
whenever unoccupied heating is required. The zone controller
will energize the fan. Since the fan is located in the primary air
stream, the fan may be rotating even if the fan is not energized.
Due to the nature of the fan blade geometry, the fan will actual-
ly rotate backwards. Energizing the fan motor while the blades
are rotating backwards will cause the fan to run backwards.
The zone controller handles this condition by closing the pri-
mary damper before starting the fan. Closing the damper will
stop any airflow which may cause the fan to rotate in reverse.
Once the fan is started, the damper will be controlled normally.
100%
MAX COOL LIMIT
(DAMPER OVERRIDE
PRESSURIZATION
MODE)
MAX HEAT LIMIT
MIN HEAT LIMIT
MIN COOL LIMIT
0%
FULL HEATING
FULL COOLING
DEADBAND
COOL
WARM
OCCUPIED
COOLING
NTFC
SETPOINT
OCCUPIED
HEATING &
MORNING
WARM-UP
SETPOINT
DAMPER
OVERRIDE-
EVACUATION
MODE
<
>
% AIRFLOW
SPACE TEMPERATURE (DEGREES)
PROPORTIONAL
HOT WATER HEAT
OPEN CLOSED
REHEAT LIMIT
LEGEND
Fig. 12 — Sequence of Operation for Single Duct Air Terminal
with Proportional Hot Water or Steam Heat
Air Source Supplying Heated Air
Air Source Supplying Cooled Air
Vista de pagina 22
1 2 ... 18 19 20 21 22 23 24 25 26 27 28 ... 43 44

Comentarios a estos manuales

Sin comentarios