41
3. Cooling, Fan Only, and Night Time Free Cool-
ing (NTFC):
a. If the zone requirement is none, then the
zone controllers shall modulate their damp-
ers to maintain their minimum cooling CFM
set point. Any zone controllers servicing
Series terminals shall also modulate their
dampers to maintain their minimum cooling
CFM set point after completing their SFTP
cycle. During the NTFC mode the zone con-
troller shall control between its heating and
cooling set points. During the other modes
the zone controller shall modulate its damper
to its occupied cooling set point. Parallel
fans shall only be enabled if the required
CFM falls below an operator adjustable
CFM limit.
b. If the zone requirement is cooling, then the
zone controllers shall modulate their air
dampers between their minimum and maxi-
mum cooling CFM set points to maintain
their cooling set point. Parallel fans shall be
disabled. Series fans shall start and control
after completing their SFTP cycle. For those
terminals that include humidity control, the
damper shall be modulate to an adjustable
maximum if the unit is occupied and heating
is not active. The local Relative Humidity
control shall be disable if the space tempera-
ture falls below the heating set point.
c. If the zone requirement is heating, then the
zone controllers shall modulate their damp-
ers to maintain their minimum cooling CFM
set point. Any zone controllers servicing
Series fans shall complete their SFTP cycle
before modulating their dampers. Any zone
controllers servicing single duct units with
reheat capability shall maintain the greater of
either the minimum cooling CFM set point
or the minimum reheat CFM set point. Zone
controllers servicing parallel units shall
enable their fans. Zone controllers servicing
Series terminals shall complete their SFTP
cycle before modulating their dampers. After
the fan starts, the damper shall be modulated
to maintain its minimum cooling CFM set
point.
4. Heat:
a. If the zone requirement is none, then the
zone controller shall maintain its minimum
heating CFM set point. Parallel fans shall be
disabled and their air damper shall be modu-
lated to maintain their minimum heating
CFM set point. Series units shall complete
their SFTP cycle checks and then modulate
its damper to maintain its minimum heating
CFM set point.
b. If the zone requirement is cooling, then the
zone controller shall modulate its damper to
maintain its minimum heating CFM set
point. Parallel fans shall be disabled. Zone
controllers servicing Series units shall com-
plete their SFTP cycle and then shall
modulate their primary damper to maintain
their minimum heating CFM set point.
c. If the zone requirement is heating, and the
zone controller is configured to use central
heat, then it shall modulate its damper
between its minimum and maximum heating
CFM set points to maintain its heating set
point. If it is not configured for central heat,
it shall maintain its minimum heating CFM
set point. Zone controllers servicing parallel
units shall enable their fan. Zone controllers
servicing Series fans, after completing their
SFTP cycle, shall modulate their damper
between their minimum and maximum heat-
ing CFM set points (if configured for central
heat). Otherwise, the zone controller shall
modulate its air damper to maintain its mini-
mum heating CFM set points.
5. Pressurization:
a. If the zone requirement is none or cooling,
then the zone controller shall maintain its
maximum cooling CFM set point. Parallel
fans shall be disabled. The damper for series
fans, after successfully completing its SFTP
cycle, shall modulate to maintain the maxi-
mum cooling CFM set point.
b. If the zone requirement is heating, and the
zone controller has been enabled to provide
local heating, then the zone controller shall
modulate its damper to its maximum cooling
CFM set point and enable its auxiliary heat.
If local heat is not available, the damper shall
be modulated to maintain its maximum cool-
ing CFM set point.
c. For series fan operations, the SFTP cycle
shall be completed before modulating the
primary air damper to its maximum cooling
CFM set point.
6. Evacuation:
During the Evacuation mode all terminal fans
shall be disabled and all dampers shall close.
Part 4 — Abnormal Conditions
4.01 The proposed system shall include the ability to detect
abnormal conditions, and to react to them automati-
cally. A return to normal conditions shall also generate
a return to normal notification and the system shall
revert back to its original control scheme before the
abnormal condition existed.
The following abnormal terminal conditions shall
automatically generate an alarm and the system shall
take the following actions:
A. If a space temperature sensor is determined by the
zone controller to be invalid, the zone controller
shall generate an alarm, default to its Cooling mode
and maintain its minimum cooling CFM set point.
B. If a relative humidity sensor is determined by the
zone controller to be invalid, the zone controller
shall generate an alarm and disable its humidity
algorithm.
C. If an indoor air quality sensor is determined by the
zone controller to be invalid, the zone controller