INPUTS/OUTPUTS
Single Duct Air Terminal Zone Controller
(33ZCVAVTRM) —
The input and output channel assign-
ments are shown in Table 2.
The zone controller provides seven analog inputs.
ANALOG INPUTS — The analog inputs consist of four ther-
mistor type inputs and two 0 to 10 VDC inputs. The thermistor
inputs conform to the nominal 10K thermistor values in
Table 1.
TRIAC OUTPUTS The zone controller has four 24-VAC
triac outputs on the baseboard. These outputs are capable of
switching 24 VAC at 1 Amp with a power factor of 0.8. Two
triacs control the primary output damper. One drives the damp-
er clockwise and the other counterclockwise. The two other tri-
acs are dedicated to the control of either proportional or two
position heat.
The specific output requirements for the air terminal appli-
cations are given in Table 3.
Table 2 — Zone Controller Inputs (33ZCVAVTRM)
LEGEND
W —
Wiper of Potentiometer
*Required whenever ducted heat is to be controlled. If monitoring of supply air is required the zone controller must be configured for heat even if
the box does not contain heat. It is also required for stand-alone operation.
Primary air sensor is required whenever unit is configured as a master zone controller and a non-CCN air source is used.
**24v connection (J4-16) is required for RH sensor only.
Table 3 — 33ZCVAVTRM Zone Controller Outputs
*These terminals provide 24 VAC-output power to the load.
The zone controller comes wired and configured for clockwise closure of the primary air damper. Do not change wiring to change rotation. The
installer should configure the rotation decision with Carrier software to ensure transducer calibration integrity.
CHANNEL
NAME
J4
TERMINATION
DESCRIPTION DEVICE
SPT
14,12 (ground) Space Temperature Sensor (33ZCT55SPT), field installed and wired 10K Thermistor
SAT
10,12 (ground) Supply Air Temperature Sensor, required for heat, field installed and wired* 10K Thermistor
SP_OFFST
12 (ground), 8
Set Point Offset Adjust, requires the use of field-installed 33ZCT56SPT
space temperature sensor
100K Potentiometer
PAT EM P
4, 6 (ground) Primary Air Temperature Factory option field installed and wired 10K Thermistor
RH/IAQ**
16 (24v), 15 (+), 13 (-) RH/IAQ Sensor Factory option, field installed and wired 0-10 VDC
DMPPOS
9 (10v), 7 (W+), 5 (-) Primary Damper Position Factory Supplied and wired with zone controller 0-10 VDC
TEST
3, 1 (GND) Used to test the output of the airflow transducer.
Airflow Sensor
(1-5 VDC)
REMOTE
2 (24 vac), J1 Pin 1
(24 vac)
Remote Occupancy Contact
Dry contact switch
with 24 vac supplied
by power connection
CHANNEL (10-13) J5 TERMINATIONS DESCRIPTION
DMPR_CCW
1*,2 Primary Damper CCW (factory wired)
DMPR_CW
2,3* Primary Damper CW (factory wired)
HEAT_ST1
4, 5 (24 VAC externally supplied) Heat Open, First Stage (field wired)
HEAT_ST2
6, 5 (24 VAC externally supplied) Heat Close, Second Stage (field wired)
2.13
.175 DIA
X .600
2.75-3.50 MOUNTING
4.00
.125 FOAM PAD
.40 O.D.
5.50'' X .250'' DIA.
STAINLESS STEEL PROBE
7/8'' DIA KNOCKOUTS (8)1.70
Fig. 4 — Primary Air Temperature Sensor Dimensions