Carrier 33ZCSECTRM Especificaciones Pagina 5

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 44
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 4
5
INPUTS
space temperature sensor
primary air damper position (factory-installed)
airflow sensor (factory installed)
field-installed remote wall sensor set point adjustment
optional supply temperature sensor (required for ducted
heat and supply air monitoring)
optional primary air temperature sensor (one per system
is required for systems which do not utilize a linkage
compatible air source)
optional IAQ sensor or relative humidity sensor
optional secondary airflow (zone pressure or dual duct)
optional remote occupancy contact
OUTPUTS
internally factory-wired damper actuator
heating (ducted or non-ducted)
— modulating (floating) heat
— up to 3 stages of electric heat
— two-position heat
fan start/stop
secondary damper actuator
POWER SUPPLY The 33ZCFANTRM requires a 24 VAC
± 10% power source rated at 40 VA (50/60 Hz).
POWER CONSUMPTION The power requirement siz-
ing allows for accessory water valves and for the fan contactor.
Water valves are limited to 8 VA on both two-position and
modulating hot water. The fan contactor is limited to 11 VA
(holding).
NOTE: If a water valve or fan contactor exceeds these limits,
or external contactors are required for electric heat, then it is
recommended a 60 VA transformer be used. The maximum
rating for any output is 20 VA.
ACCURACY Terminal airflow (nominal cfm) is rated at
1 in. wg (249 kPa) measured velocity pressure. The zone con-
troller is capable of controlling to as low as 10% or as high as
125% of nominal airflow with an accuracy of ± 3% (nominal)
at any point within the range.
HARDWARE (MEMORY)
FLASH EPROM
DIFFERENTIAL PRESSURE RANGE
0 to 2.0 in. wg (0 to 498 kPa) maximum for the onboard
flow sensor.
SPECIFIED SENSING TEMPERATURE RANGE — The
zone controller space temperature, supply temperature, and pri-
mary air temperature sensing range is –40 to 245 F (–40 to
118 C). The zone controller has an allowable control set point
range from 40 to 90 F (4 to 32 C) for heating and 45 to 99 F
(7 to 37 C) for cooling.
COMMUNICATIONS — The number of controllers is limit-
ed to 128 zones maximum, with a limit of 8 systems (Linkage
Coordinator configured for at least 2 zones). Bus length may
not exceed 4000 ft (1219 m), with no more than 60 devices on
any 1000 ft (305 m) section. Optically isolated RS-485 repeat-
ers are required every 1000 ft (305 m).
At 19,200 and 38,400 baud, the number of controllers is
limited to 128 maximum, with no limit on the number of Link-
age Coordinators.
ENVIRONMENTAL RATINGS
Operating Temperature: 32 to 140 F (0° to 60 C) at 10 to
90% RH (non-condensing)
Shipping Temperature: –40 to 185 F (–40 to 85 C) at 0 to
90% RH (non-condensing)
VIBRATION
Performance vibration: 0.014-in. (0.356 mm) peak to peak
displacement, 5 to 31 Hz; 0.75 G, 31 to 300 Hz
CORROSION
Office environment. Indoor use only.
APPROVALS
Listed under UL 916-PAZX, UL 873, and UL94-5V.
Accessories
SECONDARY TERMINAL CONTROLLER — The
33ZCSECTRM secondary terminal controller is required for
dual duct or zone pressurization applications. For zone pressure
control applications, the secondary terminal is used on a field-
supplied, single zone exhaust damper.
CONDUIT BOX — The 33ZCCONBOX conduit box pro-
vides two conduit connections to the zone controller for instal-
lations requiring the use of conduit due to local electrical codes.
SUPPLY AIR TEMPERATURE SENSOR — The
33ZCSENSAT supply air temperature sensor is required for all
ducted heating applications and stand-alone operation. The sen-
sor is optional on cooling only applications and is used for sup-
ply air monitoring. The sensor has an operating range of –40 to
245 F (–40 to 118 C).
PRIMARY AIR TEMPERATURE SENSOR — The
33ZCSENPAT primary air temperature sensor is required on a
linkage coordinator zone controller if the zone controller is not
using a CCN linkage compatible air source. The sensor is used
to monitor the equipment’s supply air temperature. The tem-
perature can be broadcast to the zone controllers which receive
information from a linkage coordinator. The sensor has an op-
erating range of –40 to 245 F (–40 to 118 C).
SPACE TEMPERATURE SENSOR WITH OVERRIDE
BUTTON The 33ZCT55SPT space temperature sensor
with override button is required for all applications. The space
temperature sensor monitors room temperature which is used
by the zone controller to determine the amount of conditioned
air that is allowed into the space.
SPACE TEMPERATURE SENSOR WITH OVER-
RIDE BUTTON AND SET POINT ADJUSTMENT —
The 33ZCT56SPT space temperature sensor with override
button and set point adjustment can be used in place of the
33ZCT55SPT space temperature sensor if local set point
adjustment is required. A space temperature sensor is re-
quired for all applications. The space temperature sensor
monitors room temperature which is used by the zone con-
troller to determine the amount of conditioned air that is
allowed into the space. The set point adjustment bar allows
up to a ± 15° F (8° C) temperature adjustment by the room
occupant.
RELATIVE HUMIDITY SENSOR — The 33AMSENRHS000
relative humidity sensor (indoor space) is required for zone hu-
midity control (dehumidification).
NOTE: The relative humidity sensor and CO
2
sensor cannot be
used on the same zone controller.
INDOOR AIR QUALITY SENSOR — Three different CO
2
sensors are available for optional demand control ventilation.
The 33ZCSENCO2 sensor is an indoor, wall mounted sen-
sor with an LED (light-emitting diode) display.
The 33ZCT55CO2 sensor is an indoor, wall mounted sen-
sor without display. The CO
2
sensor also includes a space tem-
perature sensor with override button.
The 33ZCT56CO2 sensor is an indoor, wall mounted sen-
sor without display. The CO
2
sensor also includes a space tem-
perature sensor with override button and temperature offset.
NOTE: The relative humidity sensor and CO
2
sensor cannot be
used on the same zone controller.
801
Vista de pagina 4
1 2 3 4 5 6 7 8 9 10 ... 43 44

Comentarios a estos manuales

Sin comentarios