10. Use adhesive or glue to re-attach insulation that has
pulled away from the unit during knockout removal
process.
11. For ducted applications tape should be applied along and
around all of the supply air opening knockouts to prevent
air leakage.
Step 2 — Make Piping Connections — Access to
piping is available through the access panels at the side of the
units or front of the unit. Qualified personnel in accordance
with local and national codes must perform all piping connec-
tions. Refer to Tables 1-4 for piping connections.
NOTE: It is important to have a common understanding of
which side of the unit is the right hand side and which is the
left hand side.
When facing the supply air outlet from the front of the unit
(air blowing in your face), your right hand will be on the right
side of the unit and your left hand will be on the left side of the
unit. See Fig. 65. Refer to Fig. 66 and 67 for typical piping
connections.
The supply and return piping connections of the factory-
provided valve package are either swaged for field brazing
(standard) or union fitted (optional) for field connection to the
coil.
VALVE PACKAGES — There are limitations on physical
size of pneumatic valves, quantity and type of matching
components, and required control interface. See Fig. 68.
Consult factory before ordering any special valve package
components that are not covered in this book.
Valve packages are shipped with the units or in unit cartons.
Valve packages include belled ends for field soldering to coil
connections.
All factory-furnished cooling valve packages are arranged
to position as much of the package as possible over an auxiliary
drain pan or drip lip. This helps minimize field piping insula-
tion requirements. Refer to Fig. 69-72 for pipe connection
configurations. See Table 7 for descriptions of common piping
components.
KNOCKOUT TAB
10 PLACES
DUCT BREAK
4 PLACES
KNOCKOUT TAB
TRIM LINE
a42-4301
Fig. 63 — 42SM Unit Supply Air Installation
UNIT
WALL
UNIT
INSULATION
90º
DUCT FLANGE
Fig. 64 — 42SM Unit Supply Air Installation
a42-4302
Fig. 65 — Unit End Reference