42C,D,V DRAIN CONNECTIONS — Install drain line in
accordance with all applicable codes. A continuous pitch of
1 in. per 10 ft of condensate drain line run is necessary for
adequate condensate drainage. Insulate the drain line to
prevent sweating. Extend the drain line straight from the drain
pan before making any turns. The installer must provide proper
support for the drain line to prevent undue stress on the
auxiliary drain pan.
A drain trap may be required by local codes and is recom-
mended for odor control. The differential height inlet to outlet
must be at least 1-in. wg greater than the total static pressure of
the unit. The differential height of the outlet to the bottom of
the trap must not be less than the total static pressure of the
unit. See Fig. 73 (42D) and 74 (42V).
Provide a trap of at least 2 in. near the end of the drain line
to prevent odors from entering the rooms.
WITH HAND VALVES ONLY
BALL VALVE
BALL VALVE
(2) BALL
R
S
COIL
BALL VALVE
GATE SHUT
OFF VALVE
(1) BALL
(1) GATE
R
S
COIL
BALL VALVE
BALL VALVE
(2) BALL
(1) BALANCING
R
S
COIL
BALL VALVE
(1) BALL
(1) CIRCUIT SETTER
R
S
COIL
BALANCING
VALVE
CIRCUIT SETTER
Fig. 72 — Valve Package without Motorized Control
When isolation valves only are specified, they will be brazed
to the coil stub-outs.
Check job specifications for system pressure, pressure drop
limitations and flow rate prior to selecting specific compo-
nents or valve package size (
1
/
2
in.,
3
/
4
in., etc.).
2-PIPE SYSTEM ONLY (One Valve Package) Application:
• 2 Pipe - Hydronic Heating Only
• 2 Pipe - Hydronic Cooling Only
LEGEND
*When aquastat is used for automatic changeover, bypass is
required as indicated by dashed line.
NOTES:
1. Continuous water flow, chilled water or hot water.
2. Not recommended for high humidity applications.
3. 2-Pipe System Only: Not recommended with unit-
mounted thermostat on vertical units.
4. The addition of any other component(s) wil require
swage fitting for field braze or optional union connection.
5. Packages factory furnished and installed.
6. Valves are
5
/
8
-in. ODS unless otherwise specified.
7. If an automatic flow control valve is added, it will be
located on supply line between shutoff valve and coil (or
motorized control valve, if supplied).
Balancing Valve
Ball Valve
Circuit Setter
Gate Shut Off Valve
a42-4307
CONDENSATE
PAN STUB-OUT
7/8 IN. FIELD-SUPPLIED
DRAIN EXTENSION
TRAP
2 IN. MIN
Fig. 73 — Typical Drain Line Details