Carrier 42C,V Manual de instalación Pagina 80

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 88
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 79
80
Start-up procedures vary depending on time of year (sum-
mer or winter) and building characteristics (new building/old
building, occupied/unoccupied, etc.)
Start-up in the cooling mode requires that proper care be
given to avoid condensation problems. Condensation forms on
surfaces that are colder than the dew point of the surrounding
air. If a unit is started and is piped with low-temperature chilled
water in a hot, humid atmosphere, condensation will form on
many parts of the unit. In order to avoid excessive condensa-
tion, higher temperature water should initially be used (approx-
imately 65 to 70 F) and the fan coil control set at low or medi-
um fan speed. Be sure the fan current does not exceed motor
nameplate values. Also, outside air supply fans, and bathroom
and kitchen exhaust fans should be off.
As the building temperature drops, the chilled water temper-
ature can be gradually reduced until it reaches 50 F. At this
point the outside air fans can be turned on. When the chilled
water temperature is reduced to its design point, the exhaust
fans can be turned on.
Cooling/Heating System — Prior to the water system
start-up and balancing, flush the chilled / hot water systems to
clean out dirt and debris which may have collected in the pip-
ing during construction. During the process, all unit service
valves must be in the closed position to prevent foreign matter
from entering the unit and clogging the valves and metering de-
vices. Strainers should be installed in the piping mains to pre-
vent such material from entering units during normal opera-
tion.
During system filling, air venting from the unit is accom-
plished by the use of standard manual air vent or optional auto-
matic air venting installed on the coil. Manual air vents are ba-
sically Schrader valves. For air venting, depress the valve unit
the air has vented the coil. When water begins to escape
through the valve, release the valve. Automatic air vents may
be unscrewed one turn counterclockwise to speed initial vent-
ing but should be screwed in for automatic venting after start-
up operation. See Fig. 100 and 101.
Air System Balancing — All duct stubs, grilles, filters,
and return-access panels must be properly installed to establish
actual system operating conditions BEFORE beginning air bal-
ancing operations.
Each individual unit and the attached ductwork is a unique
system with its own operating characteristics. For this reason,
air balancing is normally done by balance specialists who are
familiar with all procedures required to properly establish air
distribution and fan-system operating conditions. These proce-
dures should not be attempted by unqualified personnel.
Units with no ductwork have air volumes predetermined at
the factory by supply grille size and normally do not require air
balancing other than selecting the desired fan speed. Units fur-
nished with optional dampers on supply grilles may require
some small adjustments to “fine tune” the air delivery to each
grille. Opposed blade balancing dampers are not available for
all grilles on a unit with electric heat.
After proper system operation is established, the actual unit
air delivery and the actual fan motor amperage draw for each
unit should be recorded in a convenient place for future refer-
ence.
Water System Balancing — A complete knowledge
of the hydronic system, along with its components and con-
trols, is essential to proper water system balancing. This proce-
dure should not be attempted by unqualified personnel. The
system must be complete, and all components must be in oper-
ating condition BEFORE beginning water system balancing
operations.
Each hydronic system has different operating characteristics
depending on the devices and controls used in the system. The
actual balancing technique may vary from one system to
another.
After the proper system operation is established, the appro-
priate system operating conditions such as various water tem-
peratures and flow rates should be recorded in a convenient
place for future reference.
Before and during water system balancing, conditions may
exist due to incorrect system pressures which may result in no-
ticeable water noise or undesired valve operation. After the en-
tire system is balanced, these conditions will not exist on prop-
erly designed systems.
Water Treatment — Proper water treatment is a special-
ized industry. Carrier recommends consulting an expert in this
field to analyze the water for compliance with the water quality
parameters listed in Table 8 and to specify the appropriate wa-
ter treatment regimen. The expert may recommend typical ad-
ditives such as rust inhibitors, scaling preventative, antimicro-
bial growth agents or algae preventatives. Anti-freeze solutions
may be used to lower the freezing point.
Carriers water coil tubes and headers are constructed of
pure copper. Multiple brass alloys may be present in the valve
package, depending on unit configuration. It is the user's re-
sponsibility to ensure the tube and piping materials furnished
by Carrier are compatible with the treated water.
Failure to provide proper water quality will void the fan
coils unit's warranty.
Table 8 — Water Quality Concentrations
Controls Operation — Before proper control operation
can be verified, all other systems must be operating properly.
The correct water and air temperatures must be present for the
control function being tested. Some controls and features are
designed to not operate under certain conditions. For example,
on a two-pipe cooling/heating system with auxiliary electric
heat, the electric heater cannot be energized with hot water in
the system.
A wide range of controls, electrical options and accessories
may be used with the equipment covered in this manual. Con-
sult the approved unit submittals, order acknowledgements,
Fig. 100 — Manual Air Vent
Fig. 101 — Automatic Air Vent
WATER CONTAINING REQUIRED CONCENTRATION
Sulphate Less than 200 ppm
pH 7.0 to 8.5
Chlorides Less than 200 ppm
Nitrate Less than 100 ppm
Iron Less than 4.5 mg/l
Ammonia Less than 2.0 mg/l
Manganese Less than 0.1 mg/l
Dissolved Solids Less than 1000 mg/l
CaCO3 Hardness 300 to 500 ppm
CaCO3 Alkalinity 300 to 500 ppm
Particulate Quantity Less than 10 ppm
Particulate Size 800 micron max
Vista de pagina 79
1 2 ... 75 76 77 78 79 80 81 82 83 84 85 86 87 88

Comentarios a estos manuales

Sin comentarios