67
Aquastat
— The aquastat must be able to sense whether the
flowing water is being chilled or heated and switches a contact
closed to provide automatic summer or winter changeover for
the system. When a two-pipe cooling/heating system with
optional auxiliary electric heat is desired, an additional aqua-
stat is required.
Units with optional factory furnished and installed aquastats
may be shipped with aquastats mounted on the coil stub out. In
this situation, remove the aquatat before valve package installa-
tion. Refer Fig. 70 for factory piping diagram for proper loca-
tion when reinstalling the aquastats. If the valve package is
field supplied,the aquastat must be installed in a location where
it will sense the water temperature regardless of control valve
position. A bleed bypass should be provided for proper opera-
tion of aquastat. The bleed line allows a small amount of water
to flow from supply to return piping when the control valve is
closed for loop temperature sensing.
All field wiring must be in accordance with governing
codes and ordinances. Any modification of unit wiring without
factory authorization will invalidate all factory warranties and
nullify any agency listings. The manufacturer assumes no re-
sponsibility for any damages and/or injuries resulting from im-
proper field installation and/or wiring.
Units may be equipped with line voltage controls or
24 VAC control systems. The following descriptions are for
typical control sequences only. For detailed control operating
sequence, refer to thermostat operating instructions.
STANDARD WIRING PACKAGES
M
anual Fan Control — On vertical cabinet units, a fan-speed
switch may be furnished unit-mounted and wired. See Fig. 80.
On vertical furred-in units and horizontal units, the switch may
be shipped separately on a decorative wall plate for field
mounting and wiring. See Fig. 81.
The standard switch has LOW, MEDIUM, HIGH and OFF
positions plus an auxiliary contact to energize thermostats,
valves, dampers, etc.
NOTE: Wiring diagrams are for typical applications. If other
voltages for heaters or controls are specified, wiring may differ
from that shown. Refer to wiring diagram on unit blower hous-
ing for unit specific wiring.
T
hermostatic Electric Valve Control, 2-Pipe — A thermo-
statically controlled 2-position valve provides superior control
to fan cycling. With this control, the fan runs continuously un-
less it is manually switched to the OFF or AUTO position. The
fan must be on before the valve can be opened to supply water
to the coil.
This system can be used for normal 2-pipe changeover systems
and can also be furnished for cooling-only or heating-only ap-
plications by omitting the changeover and specifying which
application is intended. See Fig. 82 and 83 for line voltage con-
trol. See Fig. 84 and 85 for 24-v control. Wiring diagrams show
typical applications. Refer to wiring diagram on unit blower
housing for unit specific wiring.
IMPORTANT: Wiring diagrams shown depict typical
control functions. Refer to unit wiring label for specific
functions.
Fig. 80 — No Controls — Unit-Mounted 3-Speed Switch Only