Carrier 42C,V Manual de instalación Pagina 66

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 88
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 65
66
Step 3 — Make Electrical Connections —
Refer
to unit nameplate for required supply voltage, fan and heater
amperage and required circuit ampacity. Refer to unit wir-
ing diagram for unit and field wiring. See Fig. 77-79. Since
each project is different and each unit on a project may be
different, the installer must be familiar with the wiring dia-
gram and nameplate on the unit before beginning any wir-
ing. Make sure all electrical connections are in accordance
with unit wiring diagram and all applicable codes. The type
and sizing of all wiring and other electrical components
such as circuit breakers, disconnect switches, etc. should be
determined by the individual job requirements, and should
not be based on the size and/or type of connection provided
on the equipment. All installations should be made in com-
pliance with all governing codes and ordinances. Compli-
ance with all codes is the responsibility of the installing
contractor.
The fan motor(s) should never be controlled by any wiring
or device other than the factory-supplied switch or thermostat/
switch combination unless prior factory authorization is
obtained. Fan motor(s) may be temporarily wired for use
during construction only with prior factory approval and only
in strict accordance with the instructions issued at that time.
On 42S vertical stack units, the unit electrical supply is de-
signed to enter through knockouts provided in the top of the
unit and pass down through matching knockouts in the control
section top. Where space allows, power may be pulled directly
through the side of the cabinet into the control section.
All components furnished for field installation by either the
factory or the controls contractor should be located and
checked for proper function and compatibility. All internal
components should be checked for shipping damage, and any
loose connections should be tightened to minimize problems
during start-up.
Any devices such as fan switches or thermostats that have
been furnished from the factory for field installation must be
wired in strict accordance with the wiring diagram that appears
on the unit. Failure to do so could result in personal injury or
damage to components, and will void all manufacturer's
warranties.
Units with factory-supplied and factory-installed aquastats
may be shipped with the aquastats mounted on a coil stub-out.
If this is the case, remove the aquastat before installing valve
package. When reinstalling aquastats, consult the factory-
piping diagram in the submittal for proper location. If the valve
package is field-supplied, the aquastat must be installed in a
location where it will sense the water temperature regardless of
the control valve position. A bleed bypass may be required to
guarantee proper aquastat operation. The aquastat bypass line
allows a small amount of water to flow from the supply to the
return piping when the control valve is closed.
FACTORY-INSTALLED OPTIONS
Condensate Overflow Switch
— The condensate overflow
switch is used to detect a clogged condensate drain pan. The
condensate switch uses a normally closed contact to allow the
system control power to pass through the switch energizing the
water valves and fans allowing normal operation. When an
overflow condition is detected by the switch, it opens the NC
contact and de-energizes the water valve and fans.
Field
Tubing
Wet Rag
Torch
Supply
or
Return
Adaptor
(Factory Installed)
Stub
From Coil
Fig. 76 — Field Piping Connections
Fig. 77 — High Voltage Wiring Service Switch
(Side Location)
Option 1
Incoming Power
Option 2
Incoming Power
Fig. 78 — High Voltage Power Connection
(Unit Without Service Switch)
Option 3
Incoming Power
Fig. 79 — High Voltage Wiring Service Switch
(Bottom Location)
Vista de pagina 65
1 2 ... 61 62 63 64 65 66 67 68 69 70 71 ... 87 88

Comentarios a estos manuales

Sin comentarios