Table 7 — Piping Components (cont)
LEGEND
*Check all system component pressure ratings (coils, values,
pumps, etc.) with manufacturer and any applicable local or national
piping codes prior to specifying system pressure rating.
SYMBOL/SKETCH DESCRIPTION
C
V
FACTOR RATING*
STEAM
USE
1
/
2
3
/
4
PSI F
MODULATING VALVE (Optional)
(Non-Spring Return, Floating Point Actuator):
Modulating valves are designed to control the flow in
the circuit by making incremental adjustments to the
flow path within the valve.
Application — To control fluid flow in fan coil units.
On the 42DD,SG,SJ,SH commercial fan coil models,
the factory provided modulating valve has application
restrictions. In these models, the valve packages are
located in the airstream, downstream of the coil. Due
to the ambient temperature limitations of the modu-
lating valves, the valves can only be used in the units
listed above with 2-pipe cooling only systems.
4.0 300 200
N/A
MODULATING VALVE (Optional)
(Non-Spring Return, Proportional Type Actuator):
Modulating valves are designed to control the flow in
the circuit by making incremental adjustments to the
flow path within the valve.
Application — To control fluid flow in fan coil units.
On the 42DD,SG,SJ,SH commercial fan coil models,
the factory provided modulating valve has application
restrictions. In these models, the valve packages are
located in the airstream, downstream of the coil. Due
to the ambient temperature limitations of the modu-
lating valves, the valves can only be used in the units
listed above with 2-pipe cooling only systems.
4.0 300 200
N/A
MODULATING VALVE (Requires ETO)
(Spring Return): Modulating valves are designed to
control the flow in the circuit by making incremental
adjustments to the flow path within the valve.
Application — Same comments as non-spring return
except when powered, the actuator moves to the
desired position, at the same time tensing the spring
return system. When power is removed for more
than two minutes the spring returns the actuator to
the normal position.
4.0
300 200 N/A
AQUASTAT: Water temperature sensing electrical
switch. (Line Voltage Controls)
Application — Clips directly on nominal size
1
/
2
in. or
3
/
4
in. copper tubing for water temperature sensing.
Must be correctly located for proper control opera-
tion.
CHANGEOVER SENSOR: Water temperature sen-
sor thermistor.
Application — Sensor shall clamp on the outside
diameter of the pipe. Sensor plate shall bend to allow
its radius to be adjusted to fit the pipe. Sensor shall
be secured to the pipe with mounting clamp. Insulate
the mounting location of sensor on the pipe.
C
v
— Coefficient of Velocity
DX — Direct Expansion
ETO — Engineering to Order