hermostat 2-Pipe Total Electric Heat with Valve
Control — With this system, the complete heating require-
ment for the space is provided by the electric heater; the water
system is never changed over for heating. It is therefore possi-
ble, just as with 4-pipe systems, to have heating or cooling at
any time of the year.
The fan runs continuously unless it is manually switched to
OFF or AUTO position. Fan must be on before thermostat can
send signal to open chilled water valve or turn on electric
heater.
Normally, an automatic changeover thermostat with a dead
band between heating and cooling is used, but a manual
changeover thermostat is also suitable. A 2-way or 3-way valve
must also be used so that the chilled water is off whenever the
heater is on. No changeover device to sense water temperature
is necessary.
NOTE: Wiring diagrams are for typical applications. If other
voltages for heaters or controls are specified, wiring may differ
from that shown. See Fig. 89 for line voltage control. See
Fig. 90 and 91 for 24-v control. Refer to wiring diagram on
unit blower housing for unit specific wiring.
Fig. 89 — 42C,S,V (except VG), and 42D (600-1000 cfm) 2-Pipe Cooling with Total Electric Heat —
Remote/Wall-Mounted Thermostat (Line Voltage)